Lightning Arrester Model SLA-100/200 is designed for AC, and specifically for DC power supplies.

This unit is especially beneficial for protecting instruments from counter electromotive force by inductors and of coures normal lighting surges entering from power supply lines.

 

SLA-100/200

circle29_blue.gif 기술자료

dia_brown.gifPARTICULAR

DATA

dia_brown.gifModel

SLA-100-A

SLA-200-A

Discharge Voltagr

btwn lines

190V or more(peak)

410V or more(peak)

btwn lines & gnd

410V or less(peak)

Max.Surge Voltagr

btwn lines

400V or Less

800V or Less

btwn lines & gnd

800V or Less

 

dia_brown.gifResponse Time

0.1 microseconds or less

 Discharge Current

2 KA (8x20 microseconds)

dia_brown.gifMax. load Current

1.0A or 2.0A

Internal Series Resistance

Approx . 0.2Ω(including return)

Leajage Current

btwn  lines

 0.1mA or less

(at 150V DC)

 0.1mA or less

(at 300V DC)

btwn lines & gnd

  0.1mA or less (at 300V DC)

Max. Line Voltage

 120V AC,170V DC

 250V AC,350V DC

Operating Temperature

 -5Co to +55 Co

Operating Humidity

 90% RH Max . (non-condensing)

Mounting

 on rail EN50022 (35x7.5)

Size

18(W)x65(H)x62(D)

Copyright ⓒ 2003~7 SHIN HAN LEVEL. All Rights Reserved.